Delayed start OPH,0-9999 minutes
Temperature correction function OFF,-10-10°C
High temperature alarm function ACA,sound and light alarm
Specifications:
Product model:XY-T01
Power supply voltage:DC6-30V
Output type:relay output 10A
Temperature control accuracy:0.1°C
Measurement input: NTC10K/B3950
Refresh rate:0.5 seconds
Temperature range:-55-110?
Control temperature accuracy:0.1?
1.Heating Mode 'H':
When Temperature ? SetT - BackT ;Relay conduction, heating equipment begin to work;
When Temperature ? SetT, Relay disconnect, heating equipment stop work;
2.Refrigeration mode 'C':
When Temperature ? SetT + BackT ;Relay conduction, refrigeration equipment begin to work
When Temperature ? SetT ;Relay conduction, refrigeration equipment stop work;
3.High Temperature Alarm 'ALA':
When Temperature ? Alarm Temperature, The system opens the sound and light alarm, and disconnects the relay, any key stops the sound light;
4.Delay Start 'OPH':
When a normal heating or refrigeration work is done, the system starts to time T, and only after the T?OPH, the system can carry out the next round of heating or refrigeration work;
5.Temperature Correction Function OFE(-10.0 ~ 10.0?)?
The system will work for a long time and may have deviations that can be corrected by this function, Temperature = Measured + Calibration?
6.Parameter Remote Read/Set:
The parameters such as setting temperature, backlash temperature and temperature correction can be set through UART.
7.Restore factory Settings:
At the same time press the STOP, set key more than 3S, restore factory settings;
Temperature correction function OFF,-10-10°C
High temperature alarm function ACA,sound and light alarm
Specifications:
Product model:XY-T01
Power supply voltage:DC6-30V
Output type:relay output 10A
Temperature control accuracy:0.1°C
Measurement input: NTC10K/B3950
Refresh rate:0.5 seconds
Temperature range:-55-110?
Control temperature accuracy:0.1?
1.Heating Mode 'H':
When Temperature ? SetT - BackT ;Relay conduction, heating equipment begin to work;
When Temperature ? SetT, Relay disconnect, heating equipment stop work;
2.Refrigeration mode 'C':
When Temperature ? SetT + BackT ;Relay conduction, refrigeration equipment begin to work
When Temperature ? SetT ;Relay conduction, refrigeration equipment stop work;
3.High Temperature Alarm 'ALA':
When Temperature ? Alarm Temperature, The system opens the sound and light alarm, and disconnects the relay, any key stops the sound light;
4.Delay Start 'OPH':
When a normal heating or refrigeration work is done, the system starts to time T, and only after the T?OPH, the system can carry out the next round of heating or refrigeration work;
5.Temperature Correction Function OFE(-10.0 ~ 10.0?)?
The system will work for a long time and may have deviations that can be corrected by this function, Temperature = Measured + Calibration?
6.Parameter Remote Read/Set:
The parameters such as setting temperature, backlash temperature and temperature correction can be set through UART.
7.Restore factory Settings:
At the same time press the STOP, set key more than 3S, restore factory settings;