Overview
This document describes the specification of the PZEM-014/016 AC communication module,
the module is mainly used for measuring AC voltage, current, active power, frequency, power
factor and active energy, the module is without display function, the data is read through the
RS485 interface.
1.Function description
1.1 Voltage
1.1.1 Measuring range:80?260V
1.1.2 Resolution: 0.1V
1.1.3 Measurement accuracy: 0.5%
1.2 Current
1.2.1 Measuring range: 0?10A(PZEM-014); 0?100A(PZEM-016)
1.2.2 Starting measure current: 0.01A(PZEM-014); 0.02A(PZEM-016)
1.2.3 Resolution: 0.001A
1.3 Active power
1.3.1 Measuring range: 0?2.3kW(PZEM-014); 0?23kW(PZEM-016)
1.3.2 Starting measure power: 0.4W
1.3.3 Resolution: 0.1W
1.3.4 Display format:
?1000W, it display one decimal, such as: 999.9W
?1000W, it display only integer, such as: 1000W
1.4 Power factor
1.4.1 Measuring range: 0.00?1.00
1.4.2 Resolution: 0.01
5 Frequency
1.5.1 Measuring range: 45Hz?65Hz
1.5.2 Resolution: 0.1Hz
6 Active energy
1.6.1 Measuring range: 0?9999.99kWh
1.6.2 Resolution: 1Wh
1.6.4 Display format:
?10kWh, the display unit is Wh(1kWh=1000Wh), such as: 9999Wh
?10kWh, the display unit is kWh, such as: 9999.99kWh
1.6.5 Reset energy: use software to reset